BUSSMANN Effective July 2017 Technical Data 1116 Supersedes May 2002 SERIES Class T 600V open fuse blocks Flammability UL 94 V0 Features Provide 1-, 2- and 3-pole open blocks for 600 Vac Class T fuses High 200 kA RMS Sym. Short-Circuit Current Ratings Class T fuse blocks have a small foot print, providing substantial space savings in equipment Typical applications 600 V or less control systems Catalog symbol: 600 V or less individual control circuits T60 Recommended fuses: Description: JJS (see data sheet no.1029) Bussmann series T600 fuse blocks are open fuse blocks for use with Class T fuses up to 600 amps in various pole configurations from 1- to 3-poles. T600 blocks use Bussmann series JJS fuses. Specifications: Ratings Volts: 600 V Amps: Up to 600A Withstand rating: 200kA RMS Sym. Agency information UL Listed, UL 512, Guide IZLT, File E14853 CSA Certified, C22.2 No. 39, Class 6225-01, File 47235 RoHS compliant CETechnical Data 1116 Class T 600V open fuse blocks Effective July 2017 Catalog no./terminals Terminal AWG range/ Screw Box lug Amps Poles Fig. type T60030-1SR T60030-1CR 1 SR 10-18 Cu T60030-2SR T60030-2CR Up to 30 2 1 CR 2-14 Cu/Al T60030-3SR T60030-3CR 3 T60060-1SR T60060-1CR 1 SR 10-18 Cu T60060-2SR T60060-2CR 31-60 2 2 CR 2-14 Cu/Al T60060-3SR T60060-3CR 3 T60100-1C 1 T60100-2C 61-100 2 3 2/0-14 Cu/Al T60100-3C 3 T60200-1C 1 4 101-200 250kcmil-6 Cu/Al 1B0089* 3 5 T60400-1C 201-400 1 6 600kcmil-2/0 Cu/Al T60600-1C 401-600 1 7 (2) 600kcmil-4/0 Cu/Al * UL Listed, Guide IZLT, File E14853, CSA Certified Class 6225-01, File 21455M18. Dimensions in 1.44 2.59 3.75 1.44 0.55 0.33 0.55 1.16 0.33 0.55 2.31 0.33 0.5 0.22 DIAMETER, 0.5 C BORE 0.33 3.19 1.563 1.42 Figure 1. Up to 30 A 1.81 3.34 4.86 1.75 0.59 0.63 0.59 1.53 0.63 0.59 3.06 0.63 0.5 0.22 DIAMETER, 0.5 C BORE 2.94 1.63 1.47 Figure 2. 31 to 60 A 2 Eaton.com/bussmannseries